Three ways to find CFM
CFM is cubic feet of air per minute.
Bathroom up to 100 sq ft: CFM = floor area × 1
Bathroom over 100 sq ft: 50 CFM per toilet, shower or tub, 100 CFM per jetted tub
Duct: CFM = velocity (ft/min) × cross-section area (sq ft)
Air changes per hour (ACH) is how many times the room's full volume of air is replaced each hour. Air flow per hour = ACH × volume (Engineering ToolBox), and dividing by 60 turns it into per minute.
The bathroom rule comes from the Home Ventilating Institute (HVI): 1 CFM per square foot for bathrooms up to 100 sq ft, which HVI notes is about 8 air changes an hour, and the fixture count for larger bathrooms.
Worked examples
Room: a 14 × 12 ft room with 8 ft ceilings is 1,344 cubic feet. At 6 air changes per hour: 1,344 × 6 ÷ 60 = 134.4 CFM.
Bathroom: an 8 × 10 ft (80 sq ft) bathroom needs an 80 CFM fan. A 120 sq ft bathroom with a toilet, a shower and a jetted tub needs 50 + 50 + 100 = 200 CFM.
Duct: an 8 in round duct has an area of π × (4 ÷ 12)² = 0.349 sq ft. At 800 ft/min it carries 800 × 0.349 = 279 CFM.
Typical air change rates
| Space | Air changes per hour |
|---|---|
| Residences (general) | 1–2 |
| Garages, storage | 4–6 |
| Laundries | 10–15 |
| Kitchens | 15–60 |
| Homes, night cooling | 10–18 |
Figures from the Engineering ToolBox. Codes and standards such as ASHRAE 62.2 set the required ventilation for homes; follow your local code.
Getting a realistic number
- Fan ratings drop with duct length. A fan's rated CFM is at a low static pressure. Long or crooked ducts deliver less, so pick a fan rated above the target or use short, straight, smooth ducts.
- Velocity in ducts: residential supply trunks commonly run at about 700 to 900 ft/min and branches at 500 to 700 ft/min (HVAC School). Faster air is noisier.
- Measuring: airflow hoods and anemometers give the real CFM at a grille.