How the duct size is found
Airflow equals velocity times area, so the area needed is the CFM divided by the velocity. For a round duct, solve the circle area for the diameter.
Round diameter (in) = √(4 × area ÷ π) × 12
Rectangular equivalent: De = 1.30 × (a × b)0.625 ÷ (a + b)0.25
The last formula, from Huebscher and widely used in duct design, gives the round duct that has the same friction loss and airflow as a rectangular duct of sides a and b. The calculator finds, for several heights, the narrowest whole-inch width whose De is at least the round diameter.
Worked example
400 CFM at 700 ft/min needs 400 ÷ 700 = 0.571 sq ft = 82.3 sq in. Diameter = √(4 × 0.5714 ÷ π) × 12 = 10.24 in. The next standard round size is 12 in (a 10 in duct would run at 733 ft/min). For an 8 in tall rectangular duct, the width that matches 10.24 in is 11.03 in, so 8 × 12 in, whose De is 1.30 × 960.625 ÷ 200.25 = 10.66 in.
Note that the rectangular duct has more area (96 sq in) than the round one (82.3 sq in): a flat duct has more wall per unit of area, so it needs extra size to carry the same air with the same friction.
Typical velocities
| Duct | Residential velocity |
|---|---|
| Supply trunks | 700–900 ft/min |
| Branch ducts | 500–700 ft/min |
| Return grilles (face) | 500 ft/min or lower |
Velocities from HVAC School's quick guide. Lower velocity means quieter air and less friction, but bigger ducts.
Limits
This is a velocity-based starting point. A proper residential duct design (ACCA Manual D) sizes each run from the blower's available static pressure, the total equivalent length of the run and its fittings, and the friction rate, after a Manual J load calculation sets each room's CFM.