How the load is worked out
Watts are volts times amps, so dividing the total watts by the voltage gives the current. Then the breaker has to cover the load with room to spare for anything that runs for a long time.
Amps = total watts ÷ volts
Breaker must be at least: non-continuous amps + 125% × continuous amps
A continuous load is one expected to run at its maximum for 3 hours or more, like a space heater, a water heater or an EV charger. NEC 210.20(A) says the breaker's rating can't be less than the non-continuous load plus 125% of the continuous load. That's the same as saying a continuous load should use no more than 80% of a standard breaker, which is where the "80% rule" comes from (1 ÷ 1.25 = 0.8).
Worked example
A microwave (1,100 W) and a coffee maker (1,000 W) on one kitchen circuit: 2,100 W ÷ 120 V = 17.5 A. Neither runs for 3 hours, so a 20 A circuit covers it. A 1,500 W space heater left on all evening is continuous: 1,500 ÷ 120 = 12.5 A, × 1.25 = 15.6 A, so it needs a 20 A breaker even though 12.5 A is less than 15. On 240 V, 2,100 W draws only 8.75 A.
Add a 1,500 W space heater to the 1,100 W microwave instead: 2,600 W ÷ 120 V = 21.7 A. That's more than 20 A, the largest general-purpose 120 V circuit, so the answer is to put them on separate circuits.
Clothes dryers and electric water heaters are 240 V appliances. When you pick one of those, the calculator gives only the 240 V answer. A 4,500 W water heater draws 4,500 ÷ 240 = 18.75 A. NEC 422.13 treats a storage water heater as a continuous load, so 18.75 × 1.25 = 23.4 A, which rounds up to a 25 A breaker on its own circuit (30 A is also common).
Standard breaker sizes
A circuit that serves more than one load must be rated 15, 20, 30, 40 or 50 A (NEC 210.3), so with two or more loads the calculator rounds up only to those. A circuit for one load can use any standard rating in NEC 240.6(A): 15, 20, 25, 30, 35, 40, 45, 50, 60, 70, 80, 90, 100, 110, 125, 150, 175, 200 A and up. At 120 V, general-purpose circuits are 15 or 20 A, so anything over 20 A at 120 V needs to be split up or moved to 240 V.
Limitations
- Nameplate watts are a maximum. Many appliances, like refrigerators, cycle on and off and draw less on average, but the circuit still has to handle the peak.
- Motors start hard. Compressors and pumps draw several times their running current for a moment, and have their own sizing rules (NEC Article 430 and 440).
- The wire must match the breaker. A 15 A breaker needs at least 14 AWG copper, 20 A needs 12 AWG, and 25 or 30 A needs 10 AWG. Long runs may need larger wire; see the wire size calculator.
- Not a whole-house load calculation. Sizing a service or panel uses the NEC Article 220 method, with demand factors.
An estimate for planning, not a substitute for the electrical code or a licensed electrician.