Voltage drop calculator

Pick the wire, enter the one-way length, current and voltage to see how many volts are lost on the way and what percent that is.

Private: calculated on your device. Nothing you type is sent anywhere.

Next: Drop too high? Find the smallest wire that fixes it with the wire size calculator. Need the amps first? Add up the loads in the electrical load calculator.

How voltage drop is calculated

Every wire has a little resistance, so some voltage is used up pushing current along it. The longer and thinner the wire, and the more current it carries, the bigger the drop. Current flows out and back, so a single-phase circuit counts the length twice. A balanced three-phase circuit uses √3 (1.732) instead of 2.

Single-phase: VD = 2 × L × I × R ÷ 1,000
Three-phase: VD = 1.732 × L × I × R ÷ 1,000
Percent drop = VD ÷ supply voltage × 100

L is the one-way length in feet, I is the current in amps, and R is the wire's resistance in ohms per 1,000 feet. This calculator uses the DC resistance of stranded, uncoated copper and stranded aluminum at 75 °C from NEC Chapter 9, Table 8. That is the same basis as the K factors 12.9 (copper) and 21.2 (aluminum) used in the circular-mil formula.

Worked example

A 120 V, 16 A load sits 100 ft from the panel on 12 AWG copper (1.98 Ω per 1,000 ft). VD = 2 × 100 × 16 × 1.98 ÷ 1,000 = 6.34 V. As a percent: 6.336 ÷ 120 × 100 = 5.28%, so the load sees about 113.7 V. Moving up to 10 AWG (1.24 Ω) gives 2 × 100 × 16 × 1.24 ÷ 1,000 = 3.97 V, or 3.31%.

The 3% and 5% guidelines

Informational notes in the NEC (in 210.19(A) for branch circuits and 215.2(A) for feeders) suggest sizing wire so the drop is no more than 3% on a branch circuit or feeder, and no more than 5% in total from the service to the farthest outlet, for "reasonable efficiency of operation." These notes are advice, not enforceable rules, but most designers follow them. Some equipment, such as fire pumps and sensitive electronics, has its own stricter limits.

Resistance and ampacity used

SizeCopper (Ω per 1,000 ft)Aluminum (Ω per 1,000 ft)Ampacity, copper 75 °CAmpacity, aluminum 75 °C
14 AWG3.145.1720 Anot listed
12 AWG1.983.2525 A20 A
10 AWG1.242.0435 A30 A
8 AWG0.7781.2850 A40 A
6 AWG0.4910.80865 A50 A
4 AWG0.3080.50885 A65 A
3 AWG0.2450.403100 A75 A
2 AWG0.1940.319115 A90 A
1 AWG0.1540.253130 A100 A
1/0 AWG0.1220.201150 A120 A
2/0 AWG0.09670.159175 A135 A
3/0 AWG0.07660.126200 A155 A
4/0 AWG0.06080.1230 A180 A
250 kcmil0.05150.0847255 A205 A
300 kcmil0.04290.0707285 A230 A
350 kcmil0.03670.0605310 A250 A
400 kcmil0.03210.0529335 A270 A
500 kcmil0.02580.0424380 A310 A
600 kcmil0.02140.0353420 A340 A
700 kcmil0.01840.0303460 A375 A
750 kcmil0.01710.0282475 A385 A
1000 kcmil0.01290.0212545 A445 A

Resistance: NEC Chapter 9, Table 8, DC resistance at 75 °C for stranded conductors (solid 14–8 AWG wire is a little lower, so the drop shown is slightly conservative for solid NM cable). Ampacity: NEC Table 310.16, 75 °C column, for not more than three current-carrying conductors at 30 °C ambient. Small wire also has breaker limits under NEC 240.4(D): 15 A for 14 AWG copper, 20 A for 12 AWG copper, 30 A for 10 AWG copper, 15 A for 12 AWG aluminum and 25 A for 10 AWG aluminum.

Getting a realistic number

  • Measure the real route. Wire goes up walls and around corners, so it's usually longer than a straight line.
  • Use the actual load, not the breaker size, unless you're designing for the worst case.
  • AC effects are ignored. For large conductors in steel conduit, reactance adds to the drop; NEC Chapter 9, Table 9 gives AC values. For small branch-circuit wire the difference is usually small.
  • Hot wire has more resistance. Table 8 values are for 75 °C. A lightly loaded wire runs cooler, so its real drop is a bit less.

This is an estimate to help plan. Local codes and the equipment maker's instructions come first, and a licensed electrician should design and inspect any real installation.

Sources

How we checked this

Before every update, this calculator is run in a real browser with these known answers, and it must match all of them:

  • 12 AWG copper, 100 ft, 16 A, 120 V single-phase: 2 × 100 × 16 × 1.98 ÷ 1,000 = 6.34 V, 5.28% ✓
  • Same run in 10 AWG copper (1.24 Ω/kft): 3.97 V, 3.31% ✓
  • 1/0 aluminum, 200 ft, 100 A, 480 V three-phase: √3 × 200 × 100 × 0.201 ÷ 1,000 = 6.96 V, 1.45% ✓
  • Edge: 30 A on 14 AWG copper is over its 20 A ampacity ✓
  • Edge: a length of 0 asks for a length ✓

Last checked October 26, 2026. Spotted something wrong? The math is done in your browser with the formula shown on this page, so you can check any result by hand.

Add this calculator to your website (free)

Paste this code into any web page. The calculator works on your page, resizes itself, has no ads and no tracking cookies, and nothing your visitors type is sent anywhere. More about embedding.

Questions people ask

What is an acceptable voltage drop?

The NEC's informational notes suggest no more than 3% on a branch circuit or feeder and 5% total to the farthest outlet. On 120 V, 3% is 3.6 V; on 240 V it's 7.2 V.

How do I calculate voltage drop for 240 V?

The same way: VD = 2 × length × amps × ohms per 1,000 ft ÷ 1,000. The volts lost are the same as at 120 V for the same current, but they're a smaller percent of 240 V, so 240 V circuits tolerate longer runs.

Do I use one-way or round-trip length?

Enter the one-way length from the panel to the load. The formula doubles it for single-phase, because current flows out on one wire and back on the other.

Why is aluminum's drop higher?

Aluminum has about 1.6 times the resistance of copper of the same size (for 12 AWG, 3.25 vs 1.98 Ω per 1,000 ft), so it needs a larger size for the same drop.

Is voltage drop a code requirement?

For most circuits the 3% and 5% figures are informational notes, which are recommendations. A few articles, such as those for fire pumps and sensitive electronic equipment, set mandatory limits.