How pipe volume is calculated
A pipe is a long cylinder, so its volume is the inside cross-section times the length. Use the inside diameter: the nominal size (like "2 inch") is only a name.
Volume (cu in) = area × length (ft) × 12
US gallons = cubic inches ÷ 231; liters = gallons × 3.78541
A US gallon is exactly 231 cubic inches (NIST).
Worked example
100 ft of 2 in Schedule 40 steel pipe has an inside diameter of 2.067 in. Area = π × 1.0335² = 3.3557 sq in. Volume = 3.3557 × 1,200 = 4,026.8 cu in ÷ 231 = 17.43 gallons (65.99 L), or 0.174 gallons per foot. The same length of 2 in Schedule 40 PVC (average inside diameter 2.047 in) holds 17.10 gallons.
Schedule 40 sizes
| Nominal size (in) | Outside diameter (in) | Inside diameter, steel (in) | Average inside diameter, PVC (in) |
|---|---|---|---|
| ½ | 0.840 | 0.622 | 0.602 |
| ¾ | 1.050 | 0.824 | 0.804 |
| 1 | 1.315 | 1.049 | 1.029 |
| 1¼ | 1.660 | 1.380 | 1.360 |
| 1½ | 1.900 | 1.610 | 1.590 |
| 2 | 2.375 | 2.067 | 2.047 |
| 2½ | 2.875 | 2.469 | 2.445 |
| 3 | 3.500 | 3.068 | 3.042 |
| 4 | 4.500 | 4.026 | 3.998 |
| 6 | 6.625 | 6.065 | 6.031 |
| 8 | 8.625 | 7.981 | 7.942 |
| 10 | 10.750 | 10.020 | 9.976 |
| 12 | 12.750 | 11.938 | 11.889 |
Schedule 40 steel and PVC share the same outside diameter, but PVC is made to a minimum wall with some tolerance above it, so its average inside diameter is slightly smaller. Steel inside diameters are the outside diameter minus twice the nominal wall (ASME B36.10). Copper tube, PEX and Schedule 80 pipe have different inside diameters; enter yours directly.
Uses and limits
- Flushing and disinfecting lines: the volume tells you how much water fills the line.
- Glycol or antifreeze: add the volume of tanks, boilers and coils, which are often much larger than the pipe.
- Fittings add a little volume; for long runs it's small.